| Test Specifications:
|
ASTM
E330-02: Test Method For Structural Performance
Of Exterior Windows, Curtain Walls and Doors By Uniform Static Air Pressure Difference. |
| Project Scope:
|
Mr. Floyd Arnold contacted Certified Testing Laboratories (CTL) with regards
to conducting testing on one (1) Tornado SafeRoom. The test method requested is
described in the test specifications listed above. |
| Test Specimen Fabrication:
| The Tornado SaferRoom was fully assembled at Certified Testing Lab. facility by the client. The specimen was secured at the base and tested on a solid concrete foundation with ฝ x 4 Ram-set Red Head LDT anchor bolts. |
| Additional Description:
| The Tornado SafeRoom side plates, back plates, front plates and door were constructed of 10 gage galvanized steel. The roof plate was constructed of ผ thick black carbon steel. Each plate was bolted together with 1 ผ x ฝ" hexagon bolts, and nylox nuts to 2.500" x 2.500" x ผ" mounting angles. The door was mounted to the Tornado Safe room with two (2) galvanized steel custom pin hinges. The Tornado Safe room measured 60" wide x 55" high x 30" deep. One (1) operable hinged door measured 30 wide x 54 high. Two (2) galvanized steel angles were secured to the exterior face of the door. Each angle measured ผ thick x 31 long and was located at 5.000 center line from top and bottom of door. Three (3) ฝ x 20 long galvanized steel rods were utilized to latch door. Reference drawing # CTL-001 thru 007 figures 1-8 dated 6/27/06 signed and sealed by this laboratory. |
Measurement
locations

Deflection / Permanent Set was measured with Three (3) Dynavision
Laser indicators SN-S1002145, SN-S1002142, and SN-S1002143
Measurements
were taken at:
ASTM E330-02
Uniform structural load was conducted to ASTM E330-02 with no deviations to test method. Unit was tested to a Design Pressure of +/-385.0psf
|
Range of test | time | load | Perm. set | Allowable |
| Positive loads | (seconds) | psf | ||
| ฝ test load | 30 | 385.0 | ||
| Test load | 30 | 577.5 | location 1 | 0.112 N/A |
| location 2 | 0.101 N/A | |||
| location 3 | 0.057 N/A | |||
| Perm. set | Allowable | |||
| Range of test | time | load | ||
| Negative loads | (seconds) | psf | ||
| ฝ test load | 30 | 385.0 | ||
| Test load | 30 | 577.5 | location 1 | 0.010 N/A |
| location 2 | 0.012 N/A | |||
| location 3 | 0.002 N/A |
Specimens
were tested to ASTM E 1886-02 and 1996-02 with no deviation to the test
specifications. All specimens were tested to the Wind Zone 4 requirements stated
in section 5 of ASTM E 1996-02. Missile level D. The missile orientation
was perpendicular to the metal surface at impact. Each specimen was impacted with
an 8 ft., 9 lb. #2 southern yellow pine 2" x 4" at the following locations.
Type
and weight of missile: # 2 Southern Yellow Pine 2 x
4, Length approx. 96 & 9 lb.
Specimen 1 Impact No. Speed Ft/Sec. Speed Mph X Meas. Y Meas.
1. 148.3 100.0 30.0 27.0
2. 148.1 100.0 43.0 46.0
3 148.3 100.0 14.0 24.0
4 148.4 100.0 25.0 48.0
None of the impacts penetrated the specimen and the Tornado SafeRoom door remained operable.

Note:
At the conclusion of this test there were no signs of damage.
PERFORMANCE
TEST RESULTS- Cyclic
Static Air Pressure Loading
Specimen 1: ASTM E 1886-02
Specimens
were tested to ASTM E 1886-02 and 1996-02 with no deviation to the test
specifications. The specimen was tested to the requirements of section 5.4 table
1 in ASTM E 1996-02.
Note: (Only one specimen tested)
Positive loads (Design Pressure) +385.0 psf, - 385.0 psf
| Range of Test | Actual Load psf | Cycles/min. | # of Cycles |
| 0.2 0.5 | 77.0 192.5 | 3500 | 55 |
| 0.0 0.6 | 0.00 231.0 | 300 | 55 |
| 0.5 0.8 | 193.0 308.0 | 600 | 55 |
| 0.3 1.0 | 116.0 385.0 | 100 | 55 |
| 4500 cycles |
Deflection
taken center mid-span
Deflection Set
| .500" | .000" |
Negative loads
Range of Test Actual Load psf # of Cycles Cycles/min.
0.3
1.0 116.0 385.0
50 55
0.5 0.8
193.0 308.0
1050 55
0.0 0.6
0.00
231.0 50
55
0.2 0.5 77.0
192.5 3350
55
4500 cycles
Deflection taken center mid-span Deflection Set
| 9000 cycles completed | .750" | .125" |
Remarks: At the conclusion of the test there was
no damage to the Tornado SafeRoom and no visible signs of failure observed.
All the locks were operable and the door opened and closed without any
pressure being applied. The Tornado SafeRoom was tested to 450 miles
per hour = Design Pressure of 385psf = 577.5 pounds per square foot positive and
negative
Test
Date: June 14, 2006 thru June 20,
2006
Remarks: Detailed drawings were available for laboratory
records and comparison to the test specimen at the time of this report and will
be retained by CTL for a period of four (4) years. The results obtained apply
only to the specimen tested.
Certified
Testing Laboratories certified that the Tornado SafeRoom model Two Person SafeRoom
when manufactured to the specifications called out on the drawings signed and
sealed by this laboratory, will meet the criteria established by this test report.
Certified Testing Laboratories assumes that all information provided by the client is accurate and that the physical and chemical properties of the components are as stated by the manufacturer.
Certified
Testing Laboratories, Inc.
Client
Present:
Floyd Arnold- Tornado SafeRoom, Inc.
Testing
Performed & Witnessed by:
Ryan
Blakely- Certified Testing Lab.
Ted
Scanlon- Certified Testing Lab.
Kenny
Stringer- Certified Testing Lab.
Michael
Miller/ Senior Lab. Technician
Architectural Division
Ramesh Patel, P.E.